Type:Logic ICs
Condition:New
Model:PD305X
Item:1
Color Classification:Key subtraction output 0-10V inputs with switches with switch 0-5V 0-1
Renovation and construction content:Installation Engineering
This link includes three kinds of modules: each with basic and enhanced , please take the time to explain
1: 0-20mA 24V output load resistance of not more than 910 Euro
2: 0-5V output , 0-10V output current is less than 7mA
3: Key subtraction output
1 Overview
Based onRS485 Interface ,Modbus Analog output protocol control module.
IsolationRS485Interface, supportModbus-RTU Agreement.
2: Wide operating voltage :DC8V-30VPower reverse does not work. Using original MC34063A 38V switching power supply can work within , the power consumption is less than0.5W.
Current output type:0-20mA (21mA MAX), The output voltage 12V, 24V.
Voltage output type :0-5V,0-10V, ( can be customized 0-21V)
OutputAccuracy : Standard12PositionDA, the error does not exceed 5 per thousand standard value .
Optional DisplayLED:4Position0.36Inch red , direct display output value
Dimensions:88 * 72 * 59
Working temperature :-35~+50.
Using standard35mmRail mounting .
Application: analog output control, automatic control .
Can be customized for a controlled waveform generator.
Enhanced : Optional belt1-6Switch inputs and emergency preset settings.The state of the digital inputs can be used "IOModule communication tool " read.The basic model no such function .
Key operation can type :INprefix = st1 1 IN2As the output of the key changes in the use of, IN3Rapid buttons.prefix = o
Pressed aloneIN1OrIN2, Decrease or increase the output value0.01 (mA,V); Has been pressed2Seconds will change continuously.
In caseIN3Press , then pressIN1OrIN2, Decrease or increase the output value1.00 (mA,V);
Output value increased up to the maximum output capacity is no longer increased.
Output value is reduced to0So far.
Key connection as follows :

Output through software correction , if you set the output value exceeds the maximum output capacity of the module , the maximum output value flashes .
2 Common Interface Model Pictures and
Models Pictures and the interface is as follows:
A:RS485 Serial Communications A
B:RS485 Serial CommunicationsB
Power supplyV +: DC power positive
Power supplyGND: DC power supply negative common
+,-: Current or voltage output terminal
DIx: Switch input forGNDShort said the switch is closed and the internal structure is as follows :

3 Register information table and function code
3.1 Function Code03H( Read)06H( Write )
ParametersSetting registerInformation Sheet
Word Address | Byte Location | Description | Parameter Description | Property |
10H | Low8Position | Communication Configuration Initial value:00 | BIT<7:5> Retention BIT<4:3>00 =No parity 01 =Even parity10 =Odd parity (11 =Odd parity ) BIT<2:0>000 = 9600 001 = 1200 010 = 2400 011 = 4800 100 = 9600 101 = 14400110 = 19200Other combinations are not defined , in accordance with9600Deal with | RW |
High8Position | Mailing Address Initial value:01 | Setpoint range= 1To 250 Address0Broadcast address(If the value set for the communication program0Equivalent to1) | RW |
11H | | Current output value Initial value:00 | Module current voltage or current output value , after the module power output will follow this value . The value is2Whether the sign -byte integerThe unit is :uA,mV. | RW |
12H | Low8Position | Retention | | RW |
High8Position | Retention | | RW |
13H | | Switch1Corresponding output preset value Initial value:00 | The value is2Whether the sign -byte integerThe unit is :uA,mV. For example:1285H = 4741d = 4741 (uA,mV) = 4.741 (mA,V) Description: The preset is set up after the occurrence of the input when the switch is closed , the output value will be forced to default immediately . If the value is0Is prohibited linkage between the switch and the output. Priority: When multiple input switch is closed , the switch has a higher number of high priority. When forced to lift output , will be restored to11HMeans the set value . Digital input status can be read "Running Status Register" get . | RW |
14H | | Switch2Corresponding output preset value | RW |
15H | | Switch3Corresponding output preset value | RW |
16H | | Switch4Corresponding output preset value | RW |
17H | | Switch5Corresponding output preset value | RW |
18H | | Switch6Corresponding output preset value | RW |
3.2 Function Code03H( Reading )
The current operating statusRegisterInformation Sheet