Condition:New
Type:Drive IC
Model Number:PD3066-PT100/1000
Operating Temperature:-35 to +50
Supply Voltage:DC 8-30V
Model:PD3066-PT
Decoration and construction contents:Hydropower project
1.Summary
Main characteristics
The interface is fully protected, accidentally touching the 24V, and even 220V communication, will not be damaged.
Communication, collection, power supply, the three part is completely isolated.
Be based onRS485Interface,ModbusProtocol temperature acquisition module.
quarantineRS485Interface supportModbus-RTUAgreement.
SupportPT100Temperature sensor two wire, three wire connection, four wire connection.
The temperature calculation is completed inside the module, and the temperature value can be read directly. The unit is centigrade.
Measuring range:200+ 650, resolution 0.001,The accuracy can reach 0.1 between -20 and +150. The accuracy of other temperature range is better than 0.25.
Power source: DC 8-30V.
Use standard 35mm Installation way of guide rail.
Outline size:88*72*59
Operating temperature:-35+50.
Applications: liquid and gas temperature measurements.
2.Commonly used products, models, pictures, and interfaces
The pictures and interfaces are as follows:

A:RS485Serial communicationA
B:RS485Serial communicationB
Power SupplyV+:DC power positive
Power SupplyGND:DC power supply, negative pole, common end
Three wire connection:
RTD(n)+Sensor power supply, about 0.5mA Output.
RTD(n)-Sensor input.
GND:Common end of sensor.
Two wire connection:
RTD(n)+Sensor supply terminal+Measurement input, about0.5mAOutput.
RTD(n)-Need andGNDShort connection.
GND:The other end of the sensor.

3registerInformation table and function code
Three point oneFunction code03H(read),06H(write)
parameterSet registerInformation table
Word address | byte position | describe | Parameter description | attribute |
10 | low8position | Communication configuration
Initial value:00 | BIT<7:5> Retain BIT<4:3>00=No check01=Even check10=Odd check11=Odd check) BIT<2:0>000=9600001=1200010=2400011=4800100=9600 101=14400 110=19200Other combinations are not defined, in accordance with9600Handle | RW |
high8position | Postal address Initial value:01 | Set range=1reachTwo hundred and fifty address0For broadcast address(If the communication program sets the value to0Equal to1) | RW |
11H | low8position | Retain |
| RW |
high8position | Switching interval Initial value:05 | Set range3reach 9(seconds)If set to00H,01H,02HThen03HEquivalent. If you set the value above09HThen09HEquivalent. | RW |
Three point twoFunction code03H(read)
Input registerInformation table (read only attribute)
Word address | describe | Word address | describe |
20H | sensor1Temperature value | 30H | Retain |
21H | sensor2Temperature value | 31H | Retain |
22H | sensor3Temperature value | 32H | Retain |
23H | sensor4Temperature value | 33H | Retain |
24H | sensor5Temperature value | 34H | Retain |
25H | sensor6Temperature value | 35H | Retain |
26H | sensor7Temperature value | 36H | Retain |
27H | sensor8Temperature value | 37H | Retain |
28H | sensor9Temperature value | 38H | Retain |
29H | sensor10Temperature value | 39H | Retain |
2AH | sensor11Temperature value | 3AH | Retain |
2BH | sensor12Temperature value | 3BH | Retain |
2CH | sensor13Temperature value | 3CH | Retain |
2DH | sensor14Temperature value | 3DH | Retain |
2EH | sensor15Temperature value | 3EH | Retain |
2FH | sensor16Temperature value | 3FH | Retain |
Comment: invalid sensor. Return value isFC18=-1000d=-100.0
Temperature value is2A signed integer of 0 bytes, the actual temperature10Times value. The unit is centigrade.
3.3 registerFunction code03H(read) Floating point register
This set of registers enables users to read high-precision data,aboutPTModules can be easily read to0.01Temperature change at C.
Numerical value32positionfloatType, standardIEEE-754Floating-point format.The unit is centigrade.
Word address | describe |
40H | sensor1Temperature value |
42H | sensor2Temperature value |
44H | sensor3Temperature value |
46H | sensor4Temperature value |
|