Input we have 4-20ma,0-20ma,0-5v,0-10v,
please note when order,default is 0-10V
ZL-522 isoLation dual serial transfer analog module (232 & 485 rpm 0-10V 4-20mA)
Product advantage:
1, the second generation of Mornsun 3000V isolation voltage module, better performance. Isolation voltage from 1500V upgrade to 3000V, more secure;
2, ultra high-speed optical coupling chip, to meet the communication needs of high baud rate;
3, dual serial port input interface circuit, the use of multi-level protection cascade (TVS + RC filter), all for the design of industrial environment;
4, general guide rail housing, the use of more convenient
5, +12~24V DC voltage supply input, anti - Anti - ground protection.
6, improve the simulation output protection, 1000V anti intrusion protection, anti surge plus 600W TVS tube, the use of more security module;
7, standard MODBUS-RTU interface, to adapt to all the PLC module connection;
8, temperature drift is only 2ppm/ degrees C TI imported original 2 16 DAC chip, chip price over 30 yuan, accurate analog output;
9, the baud rate range: 300 ~ 115200bps (also more special requirements please);
10, all industrial design, to ensure that the use of new imported chips; temperature range: -40 degrees to 85
l Supply voltage: +12~24V DC voltage (12V power supply is weak), the power supply reverse protection;
l Communication interface: optocoupler isolation 3000 VDC, single 600W surge protection;
l Communication protocol: using RTU Modbus communication protocol;
l Zero drift: + 0.2uA/;
output | Output range | Resolution power | Accuracy | Explain |
Electric current | 0.000~22.000mA | 0.001mA | .0.01 mA | 20mAMaximum load500Omega |
Voltage | 0.000~-12.000V | 0.001V | .0.01 V | Maximum output current100mA |
lWrite single register --06
For example, channel 1 of the channel 1 analog output, that is, write the register 0x0001, the order is as follows:
01 | 06 | 0001 | 01 F4 | D8 1D |
Equipment number | Write function | Register address | Register value | check |
Among them, the set of analog data is 01 F4, that is, 0x1F4, decimal number is 500, then the output value of I=500/1000 = 0.5ma;
1D D8 is the 16 decimal value, is in accordance with CRC-16 (BISYNCH), the polynomial is x16 + x15 + x2 + 1 shield word is 0A001H
Cyclic redundancy algorithm is obtained. Please refer to the MODBUS for further information about the algorithm.
The returned data should be:
01 | 06 | 0001 | 01 F4 | D8 1D |
Equipment number | Write function | Register address | Register value | check |
l Read register --03
Read 2 device channel 1 and channel 2 of the current input value, 0x0005, 0x0006 two Register commands are as follows:
02 | 03 | 0005 | 0002 | D4 39 |
Equipment number | Read function | Register address | Register number | check |
Return data:
02 | 03 | 04 | 013202 2A | E9 BF |
Equipment number | Read function | Number of bytes | data | check |
Among them, the channel 1 is the value of 0132 0x0132, the decimal number is 306, then the input value is 306/1000 = 0.306, the same calculation method,
Can calculate the channel 2 input values.