4AI 4-channel 0-20mA 4-20mA analog acquisition module RS485 modbus RTU lightning protection anti-interference
4AI 4-channel 0-20mA 4-20mA analog acquisition module RS485 modbus RTU lightning protection anti-interference
4AI 4-channel 0-20mA 4-20mA analog acquisition module RS485 modbus RTU lightning protection anti-interference
4AI 4-channel 0-20mA 4-20mA analog acquisition module RS485 modbus RTU lightning protection anti-interference
4AI 4-channel 0-20mA 4-20mA analog acquisition module RS485 modbus RTU lightning protection anti-interference

4AI 4-channel 0-20mA 4-20mA analog acquisition module RS485 modbus RTU lightning protection anti-interference

Price:   $22.98

  • Model: ic0A3231
  • Shipping Weight: 0.2kg
  • 9999 Units in Stock

(0 reviews)
(complete orders today,deliverd around 26/04/2025)
  • Shipping time
    Shipping Worldwide.About 5-15 days.
  • means of transportation
    EMS,DHL,FEDEX,HK Post
  • Payment
    Paypal,T T,
  • Email us
    [email protected]
  • New Products
    5PCS 5V 1A MicroType-cMini 18650 TP4056 Lithium Battery Charger Module Charging Board With Protection Dual Functions Li-ion
    $4.76
    5128 Amplifier Board 5W Class D Digital Amplifier Board Mono Audio Module Low Distortion VS88715V
    $3.23
    Thermal Compound Conductive Grease Paste Silicone Plaster Heatsink HY883 6.5Wmk for CPU GPU Chipset Notebook Cooling Coolers
    $3.19
    DC 400W 15A Step-up Boost Converter Constant Current Power Supply LED Driver 300W XL4016 9A Step Down Buck Voltage Converter
    $4.12
    • Details
    • Reviews
    • Tags
    • FAQ
    Brand Name:icchipcn.com
    Condition:New
    Type:Voltage Regulator
    Model Number:MBSL4AI

    Chapter 1 Product Introduction

    1. Product overview

    The MBSL4AI?module is a 4-channel analog acquisition module, which can collect commonly used 4-channel?0-20mA?and?4-20mA?analog?signals?.?The collected analog signal data is output through the RS485 interface.?The module adopts the standard Modbus RTU communication protocol, which can be directly adapted to various upper computer configuration software, PLC, DCS, etc.

    1.?4-way single-ended analog input (DC 0-20mA/4-20mA), using 12-bit industrial-grade AD acquisition chip

    2.?RS485 MODBUS RTU standard communication is adopted, which can be networked with upper computer configuration software, PLC, industrial touch screen, etc.,?with communication status indicator

    3.?The communication circuit adopts lightning protection and anti-interference design

    4.?The RS485communication signal output interface adopts overvoltage and overcurrent double protection.

    5. It?can be widely used in signal acquisition and control of industrial field equipment.

    6.?The communication format can be set by software, and the module can be restored to factory settings after long pressing the "button" on the back of the module for 3 seconds.??

    7.?Power polarity protection


    2. Main technical indicators

    project

    technical indicators

    signal input

    1.?Analog input?channel:?4?-channel isolated acquisition

    2.?Analog input type:?0-20mA/4-20mA?analog signal

    3.?Analog input accuracy?: ±0.1

    4.?Working temperature range: -20~70℃

    5.?Resolution: 12bit

    6.?External power supply: DC9V~30V/2W

    Communication output

    1?.?Communication protocol: MODBUS-RTU

    2?.?Interface type: isolated RS485 communication, the output interface adopts overvoltage and overcurrent double protection

    3?.?Baud rate: 4800bps, 9600bps, 19200bps, 38400bps, 57600bps, 115200

    4?.?Parity bit: no parity, even parity, odd parity

    5?.?Setting method: module address, baud rate, check digit can be set by software

    6?.?Communication distance: @9600bps 1200 meters

    Module size and installation method

    1. Installation method: standard DIN rail installation or screw installation

    2. Dimensions: 100×55×32mm

    working environment

    Temperature: -20?~+55℃?Humidity: 35?~85%?(no condensation)

    Working power

    1?.?Power supply voltage: 10V ~ 30V wide range power supply, with power polarity protection

    2?.?Power consumption: less than 2W

    3. Interface definition

    PW+

    External power input positive terminal

    PW-

    External power input negative terminal

    485A

    RS485?signal A+

    485B

    RS485?signal B-

    AI1

    The positive terminal of the first analog input

    AI2

    The positive terminal of the second analog input

    AI3

    The positive terminal of the third analog input

    AI4

    The positive terminal of the 4th analog input

    AG

    Signal ground, analog input negative terminal

    4. Schematic diagram of analog input


    Chapter 2?Description of Modbus?Registers and Communication Protocol

    one.?MODBUS function codes and address ranges supported by the module

    register type

    address range

    function code

    Function code description

    input register

    30001-30004

    0x04H

    read one or more input registers

    holding register

    40001-40016


    0x03H

    read one or more holding registers

    0x06H

    Write a data to the holding register

    0x10H

    Write one or more data to holding register

    two.?Register definition description

    1.?Input register (function code:?0x04H?)

    address

    parameter

    length

    read?/?write

    minimum value

    maximum value

    illustrate

    30001

    AI1

    2

    read only

    0

    4095

    Analog input channel?1 AD?conversion value

    30002

    AI2

    2

    read only

    0

    4095

    Analog input channel?2 AD?conversion value

    30003

    AI3

    2

    read only

    0

    4095

    Analog input channel?3 AD?conversion value

    30004

    AI4

    2

    read only

    0

    4095

    Analog input channel?4 AD?conversion value

    2.?Holding registers (function code:?0x03H?,?0x06H?,?0x10H?)

    address

    parameter

    length

    read?/?write

    minimum value

    maximum value

    illustrate

    40009

    AI1

    2

    read only

    0

    4095

    Analog input channel?1 AD?conversion value

    40010

    AI2

    2

    read only

    0

    4095

    Analog input channel?2 AD?conversion value

    40011

    AI3

    2

    read only

    0

    4095

    Analog input channel?3 AD?conversion value

    40012

    AI4

    2

    read only

    0

    4095

    Analog input channel?4 AD?conversion value


    40003

    device address

    2

    read?/?write

    1

    247

    1?(default)

    40004

    baud rate

    2

    read?/?write

    1

    5

    1(4800) 2(9600)?default??3(19200) 4(38400) 5(57600) 6(115200)

    40005

    Check Digit

    2

    read?/?write

    1

    3

    1(?No parity?.)?Default?2(?Odd parity?) 3(?Even parity?)

    40007

    product version

    2

    read only

    0

    --

    year?+?month?+?day