Condition:New
Type:Voltage Regulator
Model Number:PD3060-PT100
Operating Temperature:-180 to +650
Supply Voltage:DC8-30V
Dissipation Power:9mA
Model:PD3060-PT100
Can choose:OLED PT100/OLED PT1000/OLED CU50/OLED CU100/OLED NI1000.(default OLED PT100)
Measuring range: PT type sensor: temperature -180 ° C ~ +650 ° C, resolution 0.1 ° C;
?CU10050: -50 °C ~ +150 °C; NI1000:: -60 °C ~ +250 °C
1 Summary
Main characteristics
Be based onRS485Interface,ModbusTemperature acquisition module.
Power supply, acquisition, communication three terminal isolation, standard MODUUS RTU protocol. All input interfaces have overvoltage protection.
SupportPT, Cu, NITemperature sensor two wire, three wire connection method.Three wire connection (the same as the three lead resistance) can completely eliminate the error caused by the lead resistance.
The sensing head can be up to 150 m without affecting the measured data.
The temperature calculation is completed in the module, and the temperature value can be read out directly.
Measuring range: PT type sensor: temperature-180℃+650℃, resolution 0.1℃;
??CU10050:-50℃~+150℃;NI1000::-60℃~+250℃
The accuracy can reach 0.25℃?at -20℃?to +150℃. The precision of other temperature range is better than 0.5℃.
Power supply: DC8-30V. Measured 30V power consumption 9mA, 24V power consumption 12mA, 12V power consumption 23mA, 8V power consumption 33mA.
Using standard35mmRail installation.
Outline dimension:88*72*59
Operating temperature?-35℃~+50℃.
Applications: liquid and gas temperature measurement.
2 Commonly used product model images and interfaces
A:RS485Serial communicationA
B:RS485Serial communicationB
Power SupplyV+DC power supply
Power SupplyGNDDC power supply negative, common end
Three wire connection:
RTD (n) +Sensor supply side0.5mAOutput.
RTD (n) -Sensor input.
GNDSensor common end.
Two wire connection:
RTD (n) +Sensor supply side+Measuring input0.5mAOutput.
RTD (n) -Need andGNDShort connection.
GNDThe other end of the sensor.
3registerInformation table and function code
Three point oneFunction code03H(read),06H(write)
parameterSet registerInformation table
Word address | byte position | describe | Parameter description | attribute |
10H | low8position | Communication configuration
Initial value:00H | BIT<7>Parameter protection function= 0Close= 1openSee note BIT<6:5> Retain BIT<4:3>00=No calibration01=Even parity10=Odd parity check11=Odd parity check) BIT<2:0>000=9600001=1200010=2400011=4800100=9600 101=14400 110=19200Other combinations are not defined in accordance with9600Handle | RW |
high8position | Postal address Initial value:01H | Setting range=1reachTwo hundred and fifty address0Broadcast address(If the value of the communication program is set0, equal to1) | RW |
11H | low8position | Retain | | RW |
high8position | Filter parameters Initial value:01H | Setting range=1reach16;0Equivalent to1Greater than16Equivalent to16 When the value is relatively large, you can increase the appropriate filter parameters. This parameter isPTInvalid type module. | RW |
12H | 16position | Invalid flag value Initial value:-1000 | Invalid flag value returned when sensor error,-1000Equivalent to temperature-100.This value can be redefined,See Appendix three | RW |
Hardware information register information table
Word address | byte position | describe | Parameter description | attribute
|
16H ......... 1DH | | | common8Unit,16individualBYTES. Is model information, such as:"PD3066-4W PT100","PD3065-K" "PD3064-J","PD3060 PT100" | R |