8 channel K-type thermocouple acquisition module RS485 MODBUS RTU protocol PD-3060PD3064-K
8 channel K-type thermocouple acquisition module RS485 MODBUS RTU protocol PD-3060PD3064-K
8 channel K-type thermocouple acquisition module RS485 MODBUS RTU protocol PD-3060PD3064-K
8 channel K-type thermocouple acquisition module RS485 MODBUS RTU protocol PD-3060PD3064-K
8 channel K-type thermocouple acquisition module RS485 MODBUS RTU protocol PD-3060PD3064-K

8 channel K-type thermocouple acquisition module RS485 MODBUS RTU protocol PD-3060PD3064-K

Price:   $59.97

  • Model: ic0A441
  • Shipping Weight: 0.2kg
  • 9999 Units in Stock

(0 reviews)

Please Choose:

  • WHITE
  • Gray
(complete orders today,deliverd around 26/04/2025)
  • Shipping time
    Shipping Worldwide.About 5-15 days.
  • means of transportation
    EMS,DHL,FEDEX,HK Post
  • Payment
    Paypal,T T,
  • Email us
    [email protected]
  • New Products
    Replacement New 9 Inch 2.5D GT911 Chip Touchpad For Teyes Spro Touch Screen Digitizer GPS Car Radio Multimedia Video Player
    $20.50
    New original TETyco HVDC relay contactor IHV50A5ANG50A 24V withstand 900V
    $46.98
    Original FOR X3550 M5 CPU Chip Cooling Fan 00KC909 00FK455 0KC909 0FK455 X3550M5 Server CPU Cooler Fan CPU Cooling Heatsink Fan
    $21.65
    RS485 232 serial to MBUSM-BUSMETER-BUS isolation converter module 10 from the station
    $44.69
    • Details
    • Reviews
    • Tags
    • FAQ
    Condition:New
    Type:Logic ICs
    Model Number:8 K -type
    Model:PD3060-K
    Renovation and construction content:Hydropower Engineering

    Compatibility :

    PD3060-K type thermocouple temperature acquisition module , and PD3060-PT100 temperature acquisition module , just different sensors connected

    Communication parameters are identical.

    VersusPD3015Series of temperature and humidity acquisition module communication protocolExactly the same format , test software are identical, but

    Humidity register moot.



    1.Outline



    Main features

    Based onRS485Interface ,ModbusTemperature acquisition module protocol .

    IsolationRS485Interface, supportModbus-RTUAgreement.

    Completion of the internal temperature calculation module , can be read directly temperature in Celsius degrees .

    KThermocouple Module:

    8 thermocouple MAX6675 uses a dedicated chip , support K -type thermocouple temperature sensor. High-precision cold-junction compensation.
    Measuring range : Temperature 0 ~ + 1024 , resolution 0.25 .

    Power supply: DC8-30VStatic power consumption of less than0.05W.

    Using standard35mmRail mounting .

    Dimensions:88 * 72 * 59

    Working temperature :-35~+50.

    Application: liquid , gas temperature measured in the field .




    Two pictures and interfaces


    A:RS485Serial CommunicationsA

    B:RS485Serial CommunicationsB

    Power supplyV +: DC power positive

    Power supplyGND: DC power supply negative common

    TD (n) +: Sensor positive

    TD (n) -: Sensor negative

    3Register information table and function code

    3.1Function code03H( Read)06H( Write )

    Parameter setting register information table

    Word Address

    Byte

    Location

    Description

    Parameter Description

    Property

    10

    Low8Position

    Communication Configuration



    Initial value:00

    BIT<7>: Parameter Protection0 =Shut down1 =OpenSee Note

    BIT<6:5>Retention

    BIT<4:3>00 =No parity01 =Even parity10 =Odd parity (11 =Odd parity )

    BIT<2:0>000 = 9600001 = 1200010 = 2400011 = 4800100 = 9600

    101 = 14400110 = 19200Other combinations are not defined , in accordance with9600Deal with

    RW

    High8Position

    Mailing Address

    Initial value:01

    Setpoint range= 1To250

    Address0Broadcast address(If the value set for the communication program0Equivalent to1)

    RW

    11H

    Low8Position

    Retention

    RW

    High8Position

    Retention

    RW



    3.2Function code03H( Reading )

    Input register information table ( read-only attribute )

    Word Address

    Description

    Word Address

    Description

    20H

    Sensor1Temperature value

    30H

    Retention

    21H

    Sensor2Temperature value

    31H

    Retention

    22H

    Sensor3Temperature value

    32H

    Retention

    23H

    Sensor4Temperature value

    33H

    Retention

    24H

    Sensor5Temperature value

    34H

    Retention

    25H

    Sensor6Temperature value

    35H

    Retention

    26H

    Sensor7Temperature value

    36H

    Retention

    27H

    Sensor8Temperature value

    37H

    Retention

    28H

    Sensor9Temperature value

    38H

    Retention

    29H

    Sensor10Temperature value

    39H

    Retention

    2AH

    Sensor11Temperature value

    3AH

    Retention

    2BH

    Sensor12Temperature value


    Note: The invalid return value of the sensor is FC18=-1000d=-100.0,

    The temperature value is a 2-byte signed integer that is 10 times the actual temperature. The unit is °C.