Condition:New
Type:Logic ICs
Model Number:8 K -type
Model:PD3060-K
Renovation and construction content:Hydropower Engineering
Compatibility :
PD3060-K type thermocouple temperature acquisition module , and PD3060-PT100 temperature acquisition module , just different sensors connected
Communication parameters are identical.
VersusPD3015Series of temperature and humidity acquisition module communication protocolExactly the same format , test software are identical, but
Humidity register moot.
1.Outline
Main features
Based onRS485Interface ,ModbusTemperature acquisition module protocol .
IsolationRS485Interface, supportModbus-RTUAgreement.
Completion of the internal temperature calculation module , can be read directly temperature in Celsius degrees .
KThermocouple Module:
8 thermocouple MAX6675 uses a dedicated chip , support K -type thermocouple temperature sensor. High-precision cold-junction compensation.
Measuring range : Temperature 0 ~ + 1024 , resolution 0.25 .
Power supply: DC8-30VStatic power consumption of less than0.05W.
Using standard35mmRail mounting .
Dimensions:88 * 72 * 59
Working temperature :-35~+50.
Application: liquid , gas temperature measured in the field .
Two pictures and interfaces

A:RS485Serial CommunicationsA
B:RS485Serial CommunicationsB
Power supplyV +: DC power positive
Power supplyGND: DC power supply negative common
TD (n) +: Sensor positive
TD (n) -: Sensor negative
3Register information table and function code
3.1Function code03H( Read)06H( Write )
Parameter setting register information table
Word Address | Byte Location | Description | Parameter Description | Property |
10 | Low8Position | Communication Configuration
Initial value:00 | BIT<7>: Parameter Protection0 =Shut down1 =OpenSee Note BIT<6:5>Retention BIT<4:3>00 =No parity01 =Even parity10 =Odd parity (11 =Odd parity ) BIT<2:0>000 = 9600001 = 1200010 = 2400011 = 4800100 = 9600 101 = 14400110 = 19200Other combinations are not defined , in accordance with9600Deal with | RW |
High8Position | Mailing Address Initial value:01 | Setpoint range= 1To250 Address0Broadcast address(If the value set for the communication program0Equivalent to1) | RW |
11H | Low8Position | Retention | | RW |
High8Position | Retention | | RW |
3.2Function code03H( Reading )
Input register information table ( read-only attribute )
Word Address | Description | Word Address | Description |
20H | Sensor1Temperature value | 30H | Retention |
21H | Sensor2Temperature value | 31H | Retention |
22H | Sensor3Temperature value | 32H | Retention |
23H | Sensor4Temperature value | 33H | Retention |
24H | Sensor5Temperature value | 34H | Retention |
25H | Sensor6Temperature value | 35H | Retention |
26H | Sensor7Temperature value | 36H | Retention |
27H | Sensor8Temperature value | 37H | Retention |
28H | Sensor9Temperature value | 38H | Retention |
29H | Sensor10Temperature value | 39H | Retention |
2AH | Sensor11Temperature value | 3AH | Retention |
2BH | Sensor12Temperature value | |
Note: The invalid return value of the sensor is FC18=-1000d=-100.0,
The temperature value is a 2-byte signed integer that is 10 times the actual temperature. The unit is °C.
Modbus poll test Signed integer register