Price:   $35.15

  • Model: ic0A309
  • Shipping Weight: 0.2kg
  • 9999 Units in Stock

(0 reviews)

Please Choose:

  • CM300DY-24NF
  • CM200DY-24NF
  • CM150DY-12NF
(complete orders today,deliverd around 11/07/2024)
  • Shipping time
    Shipping Worldwide.About 5-15 days.
  • means of transportation
    EMS,DHL,FEDEX,HK Post
  • Payment
    Paypal,T T,
  • Email us
    [email protected]
  • New Products
    (1-5piece) 100% New BQ25710 BQ25710RSNR BQ25710RSNT QFN-32
    $31.55
    100% New 100-000000082 100-000000083 100-000000084 100-000000085 100-000000098 100-000000099 100-000000100 101 103 104 105 BGA
    $185.55
    RP2040 Core Board TYPE-C USB-C For Raspberry Core Board 4MB RP2 for Raspberry Pi Pico Micropython 4M
    $2.75
    D2-1 diy kit Intelligent tracking the car kit D2-1 patrol car parts Electronic manufacture DIY smart car diy electronic suite
    $2.75
    • Details
    • Reviews
    • Tags
    • FAQ
    Type:Logic ICs
    Condition:New
    Model Number:8AI Compatible type

    8-channel universal analog isolated input module

    1 Product Overview

    8AI 8-channel analog universal isolated input module is a universal remote I/O product in the automation system. It realizes the isolated acquisition of 8 analog voltage and current signals through RS485 communication interface.

    This module is designed for all industrial applications, four-terminal isolation, that is, the electrical power supply, analog signal input and RS485 communication interface are electrically isolated from each other, effectively suppressing various serial and common mode interferences in the industrial field, ensuring work reliability and data precision. degree. The RS485 communication interface implements the MODBUS RTU protocol and can be directly connected to various PLCs, DCS systems, man-machine screens and various configuration software.

    The input signal of 8AI can be selected from 0~20mA, 4~20mA, 0~5V, 0~10V and other formats.

    2 Product Features

    l 8 analog inputs, 12bit resolution, acquisition accuracy ±0.1%

    l Various signal specifications input such as0~20mA, 4~20mA, 0~5V, 0~10V can be support

    l Support analog signal disconnection detection (4~20mA specification)

    l All functions are software configuration, no dial switch and internal jumper to ensure product reliability

    l Has the function of hardware forced recovery communication parameter factory configuration

    1-8AI-1

    l Full industrial lightning protection design, using magnetic isolation technology to achieve three-terminal isolation between power supply, communication port and signal input

    l MODBUS RTU communication protocol

    l DC10~30V wide range power input, anti-reverse connection

    3 Product Specifications

    8 analog inputs

    Signal specifications: 0~20mA, 4~20mA, 0~5V, 0~10V, etc.

    With wire break detection (for 4~20mA format signals)

    Sampling frequency: 100Hz

    Electrical isolation: 1500V (customizable 3000V)

    Analog input

    Physical type: RS485

    Communication protocol: MODBUS RTU

    Communication rate: 1200/2400/4800/9600/19200/38400/57600/115200bps

    Calibration method: no parity, odd parity, even parity

    Stop bits: 1 bit, 2 bits

    1500V isolation voltage

    Lightning protection and anti-jamming design

    Communication Interface

    12bit resolution, acquisition accuracy ±0.1%

    Sampled value output range: 0~4095

    0-20mA and 4-20mA current signal resolution: 5 uA

    0-5V voltage signal resolution: 1.25 mV

    0-10V voltage signal resolution: 2.5 mV

    Temperature drift: 25ppm

    Sampling output

    Nominal power supply: DC24V

    Input range: DC10~30V

    Power consumption: ≤ 2W

    Protection function: anti-reverse connection

    power input

    Module structure

    Shape structure: Adam module, 10+10-position pluggable terminal

    Installation method: DIN rail mounting

    Dimensions

    Module part: 104mm × 72mm × 26mm (excluding terminal and rail seat)

    Maximum size: 124mm × 72mm × 45mm (including terminal and rail seat)

    working environment

    Working temperature: -25 ~ +85 °C

    Ambient humidity: 10~90% RH (no condensation)

    4 indicator description

    Indicator light

    Name

    colour

    Description

    PWR

    Power indicator

    green

    Slow flashing: Power on, always on: Ready, fast flash: Restore communication configuration

    TXD

    Data transmission

    red

    send data

    RXD

    Data reception

    yellow

    Receive data

    5 Forced recovery of communication parameters factory configuration

    When the communication parameters are forgotten, or the communication parameters are changed due to misoperation, in addition to the configuration software search module, the factory configuration of the forced recovery communication parameters can also be performed. The methods and steps are as follows:

    (1) Ensure that the module has been powered off;

    (2) Short-circuit (connect) the INT terminal (terminal 6) and VIN- terminal (terminal 10) with wires; (3) Power on the module, the module power supply light flashes twice and then flashes quickly; (4) Turn off the power , remove the short wiring; (5) the module is powered, the communication parameters of the module have been restored to:

    Communication rate: 9600bps

    Stop Bit: 1 bit check mode: no local address: 1

    Warning: Short-circuiting the module in the unpowered state will not perform the above operation, and may cause permanent damage to the module!

    6 terminal arrangement and description

    Terminal

    Code

    Name

    Schematic

    1

    AI5+

    Analog 5 positive input

    2

    AI5-

    Analog 5 negative input

    3

    AI6+

    Analog 6 positive input

    4

    AI6/7-

    Analog 6, 7 negative input

    5

    AI7+

    Analog 7 positive input

    6

    INT

    Restore factory settings terminal

    7

    485A

    RS485 data A

    8

    485B

    RS485 data B

    9

    VIN+

    Power input positive

    10

    VIN-

    Power input negative

    11

    AI0+

    Analog 0 channel positive input

    12

    AI0-

    Analog 0 channel negative input

    13

    AI1+

    Analog 1 positive input

    14

    AI1-

    Analog 1 negative input

    15

    AI2+

    Analog 2 positive input

    16

    AI2-

    Analog 2 negative input

    17

    AI3+

    Analog 3 positive input

    18

    AI3-

    Analog 3 negative input

    19

    AI4+

    Analog 4 positive input

    20

    AI4-

    Analog 4 negative input