Type:Logic ICs
Condition:New
AmmoniaTransmitter
Product introduction
This transmitterBuilt in lightning protection, anti reverse, overcurrent and other multiple protection.Complete interchangeability.Be used foraccuratemeasureAmmonia concentration.The transmitter is used as slave station through industrial common interface.RS485 will air pressure.TransformationOutput.Software completeaccording tostandardMODBUS RTUserialcommunication protocolDevelopment.canVery good compatibility.WINCC,Kingview,Force control, Kunlun state, touch screen,PLCAnd other host configuration software.And hardwareAnd the third party according to the standard.The software or hardware developed by MODBUS RTU protocol.andLCD screen can be displayed on-site to display measurement data.,The functions of buzzer sound alarm prompt after exceeding the limit, alarm relay driving alarm equipment action after exceeding the limit, etc.. This paragraphTransmitter power supply and communicationOnly need1 4 core communication cables can transmit sensor data remotely.canIn constructionscenesaveOf large numberCable, the price advantage is very obvious.
Two.technical parameter
Detection gas: ammonia (NH3)
Range: 0~50ppm
Maximum measurement limit: 200ppm
Sensitivity: (0.10±0.05) uA/ppm
Resolution: 0.5ppm
Response time (T90): ≤90s
Bias: 0mV
Load resistance (recommended): 10Ω
ammonia
worktemperature:-20~60Centigrade5~95%RH
storagetemperature:-25~80Centigrade
Power supply voltage:DC7~24VRecommend:DC12V
Maximum power consumption:100mA12V, with liquid crystal (0802)
Display mode:LED indicator orLCD LCD screen
LCD screen specifications:LCD08028 character *2 line
Communication interface:RS485
Communication protocol:MODBUS RTU
Communication rate: Software settings2400, 4800, 9600, 19200, 38400, 115200etc.. default9600bps
Data format:default8N1(1 bit start bits, 8 bit data bits, 1 bit stops,nothingCheck)
Communication mode:TransmitterAs a resultMODBUS RTU slave station, master station (touch screen, PLC, host computer, etc.) uses master-slave polling mode to query the real-time data of the transmitter.
Node address:1~255Dial switch or soft switchPart setting
Number of nodes:Theoretically, the same bus is the most.128 transmitters, the actual application of up to 1/2~2/3
Transmission distance:1000 meters (RS485 communication special cable)
Before sending out the transmitteralreadyAfter three protection, ensure high temperature and humidity special.soilLong term use.
Installation: wall mounted
Product size:115*80*40Mm
Product specification selection form:
Serial number | Name | Specifications | Remarks |
1 | Ammonia transmitter | IS-TM-485-O2-1-DC | |
2 | Ammonia transmitter | IS-TM-485-O2-1-LED-DC | With LED indicator light |
3 | Ammonia transmitter | IS-TM-485-O2-1-LCD-DC | LCD with LCD (0802) |
4 | Ammonia transmitter | IS-TM-485-O2-1-LED-B1-DC | With LED indicator, 1 alarm. |
5 | Ammonia transmitter | IS-TM-485-O2-1-LED-B2-DC | With LED indicator, 2 alarm. |
6 | Ammonia transmitter | IS-TM-485-O2-1-LCD-B1-DC | With LCD indicator, 1 alarm. |
7 | Ammonia transmitter | IS-TM-485-O2-1-LCD-B2-DC | With LCD indicator, 2 alarm. |
8 | High range ammonia transmitter | IS-TM-485-O2-2-DC | |
9 | High rangeAmmonia transmitter | IS-TM-485-O2-2-LED-DC | With LED indicator light |
10 | High rangeAmmonia transmitter | IS-TM-485-O2-2-LCD-DC | LCD with LCD (0802) |
11 | High rangeAmmonia transmitter | IS-TM-485-O2-2-LED-B1-DC | With LED indicator, 1 alarm. |
12 | High rangeAmmonia transmitter | IS-TM-485-O2-2-LED-B2-DC | With LED indicator, 2 alarm. |
13 | High rangeAmmonia transmitter | IS-TM-485-O2-2-LCD-B1-DC | With LCD indicator, 1 alarm. |
14 | High rangeAmmonia transmitter | IS-TM-485-O2-2-LCD-B2-DC | With LCD indicator, 2 alarm. |
15 | | | |
16 | Customizing | IS-TM-485-O2-X-C-DC | Product function customization |
17 | | | |
Three.Usage method
The followingWIN10 64bit system is introduced as an example.
1.Hardware preparation
1.1 DC power supply(Not include):
7~24V, 100mA above


1.2 RS485 converter(Not include):
Prepare a good quality.RS485 converter (preferably active RS485 converter), or other hardware with RS485 interface (touch screen, PLC, industrial computer or customer development hardware equipment), USB to RS485 converter or RS232 to RS485 converter can be, must ensure that the converter can send and receive data in two directions, some monitoring converter is single It is impossible to use communication. When buying, you must ask the seller clearly.

One point threeDownload correspondingRS485If the driver of the converter is installed properly, make sure that the driver is installed correctly and that there is no yellow exclamation mark in front of the installed driver.

aboutWIN10 64Bit system, installation:

One point fourLook at the computer.O2MSlogans for earlier desktops or notebooksDB9For public equipment,O2MSlogans are generallyO2M1See through the following ways;
Right click My computer- - >attribute- - >Device manager- - >Double click port (O2MandLPT)- > USB-SERIAL CH340 (O2M6)
O2M 6That's what we need later.O2M Slogans;



2,Hardware connection
Connect the test cable reserved by the transmitter out of the factory to all the test equipment correctly, and pay attention to the cable core line not to be misconnected.
red7~24V+
Blue or blackGND
yellowRS485 A/ (+)
green RS485 B/ (-)