Digital output module switch module isolated 16 DO RS485 MODBUS communications
Digital output module switch module isolated 16 DO RS485 MODBUS communications
Digital output module switch module isolated 16 DO RS485 MODBUS communications

Digital output module switch module isolated 16 DO RS485 MODBUS communications

Price:   $29.18

  • Model: ic0A693
  • Shipping Weight: 0.2kg
  • 9999 Units in Stock

(0 reviews)
(complete orders today,deliverd around 25/04/2025)
  • Shipping time
    Shipping Worldwide.About 5-15 days.
  • means of transportation
    EMS,DHL,FEDEX,HK Post
  • Payment
    Paypal,T T,
  • Email us
    [email protected]
  • New Products
    10PCS 74HC138D SOP16 74HC138 SOP SN74HC138DR SMD
    $0.75
    10PCSLOT 74HC08D SOP14 74HC08 SN74HC08DR SOP-14 SMD New and Original IC In Stock
    $0.87
    1PCS B0505S-1W B0505S-2W B0505S-1WR2 B0505LS-1WR2 B0505LS-1WR3 5VTo5V Converter DC DC Power Module Converter 1000VDC Isolation
    $1.80
    Voltage Regulated Module Radiator and Fan heatsink
    $29.21
    • Details
    • Reviews
    • Tags
    • FAQ
    Type:Logic ICs
    Condition:New

    if want manual ,please contact us ,thank you.

    I. Product Overview

    l 16Opto-isolated digital outputs (NPN open collector transistor output )

    l Using RS485 MODBUS RTU standard communication , networking and configuration software can be , PLC, industrial touch screen , etc.

    l With communications and output status indicator

    l Communication circuit lightning , anti-jamming design

    l Signal acquisition and control can be widely used in industrial field devices

    l Normal use of three-year warranty

    Second, the main parameters

    l Digital output channels 16 (NPN transistorOpen collectorOutput ,500mA)

    l Operating temperature range -20 ~ 70

    l External power supply DC 9V ~30V / 2W

    l 1500VDC isolation protection

    l Standard DIN mounting rail or screw mounting

    l Dimensions 125 × 73 × 35mm

    Third, the interface definition

    AVcc

    The positive terminal of the external power input

    AGnd

    Negative external power input terminal

    DO_01

    The first digital outputs

    DO_02

    The first two digital outputs

    DO_03

    3 digital outputs

    DO_04

    4 digital outputs

    DO_05

    5 digital outputs

    DO_06

    6 digital outputs

    DO_07

    Section 7 digital outputs

    DO_08

    Section 8 digital outputs

    DO_09

    Article 9 digital outputs

    DO_10

    The first 10 digital outputs

    DO_11

    11 digital outputs

    DO_12

    12 digital outputs

    DO_13

    The first 13 digital outputs

    DO_14

    14 digital outputs

    DO_15

    15 digital outputs

    DO_16

    16 digital outputs

    485A

    RS485Signal A +

    485B

    RS485Signal B-

    Fourth, the digital output application diagram


    Five , communications instructions

    1,Communication Parameters ( factory default ): 9600, N, 8,1

    Parameters

    Description

    9600

    Baud Rate

    N (No parity )

    Parity bit

    8

    Data bits

    1

    Stop bits

    2, The digital output signal control commands ( multiple control ) :

    Send : 01 0F 00 00 00 10 02 21 86 7B D2 ( case / 16 hex )

    Data

    Bytes

    Data Description

    Remarks

    01

    1

    Module address

    Address range 01-FE

    0F

    1

    Function Code

    0F-Write multiple coils

    0000

    2

    Coil address (0x type )

    0000-Coil start address

    0010

    2

    Write coil length

    0010-Write 16 coils

    02

    1

    Write data byte

    02Write two bytes of data

    2186

    2

    Write data

    2186-Write 16 coils output state

    7BD2

    2

    CRCChecksum

    All the data in front of the CRC

    Reception : 01 0F 00 00 00 10 54 07 ( cases / 16 hex )

    Written data "21" , is converted into a binary number " 00100001 " , from left to right correspond to eight digital output signal status DO_08-DO_01 of written data " 86 " is converted into 2 into system number is " 10000110 " , from left to right respectively 8 digital output signal status DO_16-DO_09 , that DO_16, DO_11, DO_10, DO_06, DO_01 there is output , no other channel output , the module receives the correct command after making the appropriate action based on the command and response command sent back to the host , indicating successful communication

    3, The digital output signal control commands ( individual control ) :

    Send : 01 05 00 00 FF 00 8C 3A ( case / 16 hex )

    Data

    Bytes

    Data Description

    Remarks

    01

    1

    Module address

    Address range 01-FE

    05

    1

    Function Code

    05-Single Coil

    0000

    2

    Coil address (0x type )

    0000-Digital output (DO_01) coil address

    0001-Digital output (DO_02) coil address

    0002Digital output (DO_03) coil address

    0003-Digital output (DO_04) coil address

    0004-Digital output (DO_05) coil address

    0005Digital output (DO_06) coil address

    0006-Digital output (DO_07) coil address

    0007-Digital output (DO_08) coil address

    0008-Digital output (DO_09) coil address

    0009-Digital output (DO_10) coil address

    000A-Digital output (DO_11) coil address

    000B-Digital output (DO_12) coil address

    000C-Digital output (DO_13) coil address

    000D-Digital output (DO_14) coil address

    000E-Digital output (DO_15) coil address

    000F-Digital output (DO_16) coil address

    FF00

    2

    Write data

    FF00-Coil open , 0000- coil off

    8C3A

    2

    CRCChecksum

    All the data in front of the CRC

    Reception : 01 05 00 00 FF 00 8C 3A ( case / 16 hex )

    After the module receives the correct command , make the appropriate action based on the command and response command sent back to the host , indicating successful communication

    4, Digital output status acquisition command :

    Send : 01 01 00 00 00 10 3D C6 ( case / 16 hex )

    Data

    Bytes

    Data Description

    Remarks

    01

    1

    Module address

    Address range 01-FE

    01

    1

    Function Code

    01-Read coil status

    0000

    2

    Coil address (0x type )

    0000-Coil start address

    0010

    2

    Read Coil length

    0010-Read 16 coil state

    3DC6

    2

    CRCChecksum

    All the data in front of the CRC

    Reception : 01 01 02 21 86 20 0E ( case / 16 hex )

    Data

    Bytes

    <