Industrial grade Full isolated thermal resistance temperature acquisition module transmitter PT100 PT1000 CUGEBA to RS485 MODBUS
Industrial grade Full isolated thermal resistance temperature acquisition module transmitter PT100 PT1000 CUGEBA to RS485 MODBUS
Industrial grade Full isolated thermal resistance temperature acquisition module transmitter PT100 PT1000 CUGEBA to RS485 MODBUS
Industrial grade Full isolated thermal resistance temperature acquisition module transmitter PT100 PT1000 CUGEBA to RS485 MODBUS

Industrial grade Full isolated thermal resistance temperature acquisition module transmitter PT100 PT1000 CUGEBA to RS485 MODBUS

Price:   $53.95

  • Model: ic0A945
  • Shipping Weight: 0.2kg
  • 9999 Units in Stock

(0 reviews)

Please Choose:

  • 12CH 20mA
  • 12CH(4-20mA)
  • 12CH 30V
  • 12CH 10V
  • 12CH 5V
  • 12CH 250mA
  • 8CH(20mA) 4CH(30V)
  • 8CH(20mA) 4CH(10V)
  • 8CH(20mA) 4CH(5V)
(complete orders today,deliverd around 25/04/2025)
  • Shipping time
    Shipping Worldwide.About 5-15 days.
  • means of transportation
    EMS,DHL,FEDEX,HK Post
  • Payment
    Paypal,T T,
  • Email us
    [email protected]
  • New Products
    Sensor de humedad del suelo, medidor de humedad, transmisor, 4-20mA
    $62.66
    Combustible Gas Safe Alarm Sensor Portable Natural Gas Leak Detector Propane Butane Methane Tester
    $12.38
    10PCS IRFP150N IRFP150 TO-247
    $7.40
    ESP32 0.96 Inch Blue OLED Digital Display Bluetooth WIFI Kit Module CP2102 32M Flash Internet Development Board For Arduino
    $12.36
    • Details
    • Reviews
    • Tags
    • FAQ
    Condition:New
    Type:Logic ICs

    Industrial grade

    1.6 channels

    2. Self-correction technology

    3.24 bit ADC

    4. Modular isolation

    5. Support 2 wire/3 wire/4 wire


    Product Introduction

    This is an industrial-grade thermal resistance temperature collector, which can freely access various types of thermal resistance, such as PT100, PT1000, PT500, PT800, Cu50, Cu100, Ge53, BA, etc., supporting 2-wire, 3-wire and 4-wire Three wiring methods. The collector has a built-in excitation source, dynamic compensation and wire compensation technology to make the measurement more accurate. Communication uses RS485 interface, MODBUS-RTU protocol, supports access to configuration software, PLC system, text screen, etc., which can realize rapid networking.


    Specifications:

    Thermal resistance input

    Number of input channels: 6 channels

    Thermal resistance type: PT100, PT1000, PT500, PT800, Cu50, Cu100, Ge53, BA1, BA2 (the input type can be selected by the configuration tool)

    Support three wiring modes: two-wire, three-wire and four-wire

    Acquisition accuracy: ±(0.1%+01℃)

    ADC bits: 24bit

    Sampling frequency: ≤15HZ

    Communication Interface

    Interface type: RS485

    Interface input impedance: 1/8 unit load, allowing 256 terminal devices on the bus

    Communication protocol: MODBUS-RTU

    Power supply

    Input voltage: 6V-36V DC

    Operating power consumption: 15mA@12V

    Working environment

    Working temperature: -40℃~+85℃

    Working humidity: 0-95%, non-condensing

    Display function

    Display specifications: 128×64 OLED liquid crystal display

    Display content: The first line displays the key parameters of equipment operation such as serial port parameters and thermal resistance type. The 24th line patrol displays the collection results.

    Safeguard

    Power interface: overvoltage protection, overcurrent protection and anti-reverse connection protection

    Communication interface: short circuit protection, TVS protection and ESD protection

    Acquisition interface: TVS protection and ESD 15KV (contact) 20KV (air) protection

    Features

    Strong anti-interference ability: analog-digital isolation avoids interference from digital circuits; integrated 50HZ notch can filter interference from power systems

    No self-heating error: use extremely small excitation current to avoid errors caused by thermal resistance self-heating

    Compatible with various thermal resistances: with programmable excitation current and PGA, support users to configure thermal resistance types by themselves

    Self-calibration function: with temperature compensation and self-calibration function

    Mechanical properties

    Installation method: DIN35mm rail installation

    Dimensions: 121X37X70mm (length X width X height)




    Interface and wiring instructions

    VCC: positive power supply

    GND: negative power supply

    A (+): RS485 positive or RS232-TXD (customized)

    B (-): RS485- negative electrode or RS232-RXD (customized)

    GND: Communication port GND

    INx+: Thermal resistance input positive

    INx-: thermal resistance input negative

    COM: Thermal resistance input common terminal