Switch output module 8 relay output isolation type MODBUS RTU RS485 communication
Switch output module 8 relay output isolation type MODBUS RTU RS485 communication
Switch output module 8 relay output isolation type MODBUS RTU RS485 communication
Switch output module 8 relay output isolation type MODBUS RTU RS485 communication

Switch output module 8 relay output isolation type MODBUS RTU RS485 communication

Price:   $34.33

  • Model: ic0A4968
  • Shipping Weight: 0.2kg
  • 9999 Units in Stock

(0 reviews)
(complete orders today,deliverd around 25/04/2025)
  • Shipping time
    Shipping Worldwide.About 5-15 days.
  • means of transportation
    EMS,DHL,FEDEX,HK Post
  • Payment
    Paypal,T T,
  • Email us
    [email protected]
  • New Products
    5PCS IPA6R190C6 6R190C6 TO-220
    $4.00
    2pcslot RT8249AGQW RT8249A 2Q=2D 1C 1R 2C 2J QFN20 new
    $3.50
    Mini DC-DC 12-20V To 5V 3A Step Down Power Supply Module Buck Converter Adjustable Efficiency 97.5%
    $0.50
    74HC4051 8 channel Analog Multiplexer Selector Module Multiplexers Distributor Resolver
    $0.50
    • Details
    • Reviews
    • Tags
    • FAQ
    Model Number:MB8RO
    Type:Logic ICs
    Condition:New
    type of output:8 normally open relay output
    Contact capacity:10A 250V , 3A inductive load
    Communication type:RS485 MODBUS-RTU
    Characteristic:Signal acquisition, RS485 communication, the main power of mutual isol
    Technology:Industrial patch design

    MB8RO 8 way relay output module, relay can be controlled through the MODBUS bus, the relay can be set on the electric load prefabricated state, or set a power load last relay power down state; control interface for the isolation of RS485, using Modbus-RTU communication, direct fit PLC, DCS and domestic various configuration software.

    The first chapter product introduction

    A. Summary

    MB8RO 8Road relay output module, the relay can be controlled through the MODBUS bus, the control interface for the isolation of RS485, the use of Modbus-RTU communication, directly with the PLC, DCS, and various domestic configuration software, etc..

    The relay output, the power supply and the RS485 communication electrical signals are isolated from each other, which can effectively restrain all kinds of mode and common mode interference, and ensure the reliability of the module.

    Two. Characteristic

    One Using Modbus-RTU protocol.

    2. Relay output, power supply, RS485 communication electrical signals isolated from each other.

    Three RS485The communication signal output interface is protected by the overvoltage and overcurrent.

    4. Power polarity protection.

    Three. Technical index

    project

    parameter

    signal output

    1Output channel: 8 normally open relay output

    2Load capacity: resistive load 250V/10A inductive load 250V/3A

    FiveRelay coil and contact isolation voltage: 1500V

    Communication output

    1Communication protocol: MODBUS-RTU

    2Interface type: isolated RS485 communication, the output of the interface using the overvoltage and overcurrent protection

    3Baud rate: 1200BPS, 2400bps., 4800bps, 9600bps, 19200bps

    38400bps57600bps, 115200bps.

    4Check bit: no parity check, parity check

    5. setting: module address, baud rate, parity bit is set up by the software

    6Communication distance: 9600bps 1200 meters

    SevenIsolated voltage: 1500V

    Module size

    Separate module size: 115mm*90mm*40mm

    Installation method

    Standard DIN guide rail installation

    work environment

    Temperature: -10 ~ +55 temperature humidity: 35~85% (not dew)

    Working power supply

    1Power supply voltage: 10V~30V wide range of power supply, with the power supply polarity protection

    2Power consumption: less than 3W

    Four. Product appearance

    Five. External wiring diagram

    1. Relay output method


    2. Communication and power supply connection

    Six. Module indicator lamp and switch function specification

    1. POW/SET;Module working status indication

    A.Green light: the module works in the running state. B. red light: the module is configured to write parameters, need to re power up.

    2. TXD/RXD:Communication status indication

    A.The green light flashes: the communication receives the data B. red light flashes: the module is sending data

    C.The green light is always on: DATA+ and DATA- on the communication line RS485 line is connected to the reverse or the connection is broken.

    Three Module right reset switch

    1) When the communication parameters (module address, baud rate, parity bit) do not know or communication parameter misspecification, and can not establish contact module communication, the solution is to reset the communication parameters; we use the clip to hold the reset switch is not open, 5 seconds after the [POW/SET] module of the red indicator lights, release the reset switch, the communication the parameters have been reset, as long as the power supply module after the restart time, the communication parameters of the module has been reset.

    2) Communication parameters after reset: Address: 1, baud rate: 9600bps, parity: No.

    Seven. Principle block diagram


    Eight. MODBUSRegister description

    1. Module supports MODBUS function code

    Code

    Meaning

    operation

    0x01H

    Read more than one coil register

    Read the values of one or more coil registers

    0x03H

    Read more than one hold register

    Read one or more of the value of the register.

    0x05H

    Write a coil register

    Write the value of a coil register

    0x 06H

    Write a single hold register

    Write a data to hold register

    0x0FH

    Write one or more coil registers

    Write one or more of the value of the coil register

    0x 10H

    Write more than one hold register

    Write one or more data to hold registers

    2. Register definition description

    1) Coil register0x01H,0x05H,0x0FH)

    address

    parameter

    read/write

    minimum value

    Maximum value

    Explain

    00001

    RO0

    Read and write

    0

    1

    Relay output0

    00002

    RO1

    Read and write

    0

    1

    Relay output1

    00003

    RO2

    Read and write

    0

    1

    Relay output2

    00004

    RO3

    Read and write

    0

    1

    Relay output3

    00005

    RO4

    Read and write

    0

    1

    Relay output4

    00006

    RO5

    Read and write

    0

    1

    Relay output5

    00007

    RO6

    Read and write

    0

    1

    Relay output6

    00008

    RO7

    Read and write

    0

    1

    Relay output7

    2) Hold register0x03H,0x06H,0x10H)

    address

    parameter

    read/write

    minimum value

    Maximum value

    Explain

    40065

    Equipment type

    read-only

    0

    256

    2 (MB8ROModule)

    40066

    Equipment status

    read-only

    0

    0x0101

    Bit4Reset button state

    Bit0Module reset request flag

    40067

    Module voltage

    read-only

    0

    300

    0.0-29.9V

    40069

    product version

    read-only

    0

    65535

    Hardware version(high8position+)Software version(low8position)

    40070

    production information

    read-only

    0

    65535

    year(high8position+)Batch number(low8position)

    40071

    Module address

    read/write

    1