Swiss SENSIRION imported temperature and humidity sensor SHT10, the sensor acquisition of high precision, good consistency, accuracy is guaranteed! Industrial design ideas, wide voltage DC9~30V input; module acquisition of temperature and humidity signal data, through the RS485 interface output; module using Modbus-RTU communication, can be adapted to PLC, DCS and a variety of configuration software
A. Summary
MB1TH 1Road surface humidity acquisition module, the Swiss imports of SENSIRION temperature and humidity sensor SHT10/11, the sensor with high acquisition accuracy and good consistency; temperature and humidity data acquisition module signal to the output through a RS485 interface module; using Modbus-RTU communication, can be adapted to PLC, DCS and a variety of configuration software.
Through the software can set the alarm value of the temperature and humidity module, such as the emergence of an emergency problem can prompt the user to deal with the problem and locate the position of the alarm module. The user can set the alarm value of the upper and lower limits of temperature and humidity, and the temperature and humidity limit alarm function can be opened or closed separately.
Can be used for cold storage temperature and humidity data acquisition, vegetable greenhouses, animal breeding, industrial environment monitoring, barn temperature and humidity monitoring, a variety of environmental temperature data acquisition and control, etc..
Two. Characteristic
1. Swiss SENSIRION imported temperature and humidity sensor SHT10, high precision, good consistency.
2. Increase the temperature and humidity on the lower limit alarm function to facilitate the user to deal with the problem, and locate the fault location.
Three Using standard Modbus-RTU protocol, can be adapted to PLC, DCS and a variety of configuration software, etc..
4. Communication protection: RS485 communication signal output interface using overvoltage and over current dual protection.
Five Temperature and humidity out of limit alarm, temperature and humidity limit alarm, communication format can be set through the software.
Six Power polarity protection.
Three. Technical index
project | parameter |
Temperature and humidity signal input | 1Input channel: 1 channel temperature and humidity signal acquisition 2Sensor type: SHT10 (Swiss SENSIRION) 3Sampling rate: a signal acquisition per 5mS. 4Measurement range: temperature -40 ~ 55wetDegree 0-100% (RH) relative humidity 5Resolution: temperature 0.1wetDegree 0.1% (RH) 6Accuracy: temperature 0.5wetDegree + 2% (RH) 25C |
A burglar alarm | 1. Piezoelectric alarm |
RS485 Communication output | 1Communication protocol: MODBUS-RTU 2Interface type: RS485 communication, the output of the interface using the overvoltage and overcurrent protection 3Baud rate: 1200. 2400, 4800, 9600, 38400, 57600, 19200, and 115200bps 4Check bit: no parity check, parity check 5. setting: module address, baud rate, parity bits can be set by software |
Module size | 65mm*46mm*28.3mm |
Installation method | Standard DIN guide rail installation (35mm Guide) |
work environment | Temperature: -10 ~ +55 temperature humidity: 35~85% (not dew) |
Working power supply | 1Power supply voltage: 10V~30V wide range of power supply, with the power supply polarity protection 2Power consumption: less than 0.5W |
Four. Product appearance

Five. Module indicator lamp and switch function specification
1. POW/SET;Module working status indication
A.Green light: the module works in the running state. B. red light: the module has the configuration parameters have been written, need to re power up.
2. TXD/RXD:Communication status indication
A.The green light flashes: the communication receives the data B. red light flashes: the module is sending data
C.The green light is always on: DATA+ and DATA- on the communication line RS485 line is connected to the reverse or the connection is broken.
Three Internal upper left corner reset switch
A. When the communication parameters (module address, baud rate, parity bit) do not know or communication parameter misspecification, and can not establish contact module communication, the solution is to reset the communication parameters; we use the clip to hold the reset switch is not open, 5 seconds after the [POW/SET] module of the red indicator lights, release the reset switch, the communication the parameters have been reset, as long as the power supply module after the restart time, the communication parameters of the module has been reset.
B. Communication parameters after reset: Address: 1, baud rate: 9600bps, parity: No.
Six. Wiring diagram

Seven. Principle block diagram

The second chapterModbusRegister and communication protocol
A. Module supports MODBUS function code and address range
Register type | Address range | Function code | Functional code description |
Open input register | 10001-10004 | 0x02H | Read one or more open input registers |
Input register | 30001-30004 | 0x04H | Read one or more input registers |
Hold register | 40033-40037 40065-40076 40129-40132 | 0x03H | Read one or more hold registers |
0x06H | Write a data to hold register |
0x10H | Write one or more data to hold register |
Two. Register definition description
1. Open volumeregister(0x02H)
address | parameter | read/write | minimum value | Maximum value | Explain |
10001 | DI0 | read-only | 0 | 1 | Temperature upper limit alarm value |
10002 | DI1 | read-only | 0 | 1 | Temperature lower limit alarm value |
10003 | DI2 | read-only | 0 | 1 | Humidity upper limit alarm value |
10004 | DI3 | read-only | 0 | 1 | Humidity limit alarm value |
2. Input register(function code: 0x04H)
address | parameter | Read / write | minimum value | Maximum value | Explain |
30001 | temperature | read-only | -50.0 | 550 | The temperature is 0.1 degrees C /bit |
30002 | humidity | read-only | 0 | 1000 | Humidity value 0.1% (RH) /bit |
3. Hold registerFunction code:0x03H0x06H, 0x10H)
address | parameter | Read / write | minimum value | Maximum value | Explain |
40065 | Equipment type | read-only | 0 | 256 | 0x0A(MB1TH 1Road surface humidity acquisition module) |
40066 | Equipment status | read-only | 0 | 0x0101 | Bit4Reset button state Bit0Module reset request flag |
40067 | Module voltage | read-only | 0 | 300 | 0.0-29.9Veach0.1V bit |
40068 | Module temperature | read-only | 0 |