Thermocouple acquisition module supports 8 thermocouple 4 road temperature acquisition module RS485 MODBUS
Thermocouple acquisition module supports 8 thermocouple 4 road temperature acquisition module RS485 MODBUS
Thermocouple acquisition module supports 8 thermocouple 4 road temperature acquisition module RS485 MODBUS

Thermocouple acquisition module supports 8 thermocouple 4 road temperature acquisition module RS485 MODBUS

Price:   $58.45

  • Model: ic0A943
  • Shipping Weight: 0.2kg
  • 9999 Units in Stock

(0 reviews)
(complete orders today,deliverd around 25/04/2025)
  • Shipping time
    Shipping Worldwide.About 5-15 days.
  • means of transportation
    EMS,DHL,FEDEX,HK Post
  • Payment
    Paypal,T T,
  • Email us
    [email protected]
  • New Products
    Xhorse VVDI2 VVDI Super Chip XT27A01 XT27A66 Transponder for ID46474D454647634E 644C8C8A43T3 chips 10pcslot
    $36.00
    10Pcslot xt27 xt27a super chip xt27c75 xt27a01 SUPERCHIP VVDI CHIPS
    $53.86
    Xhorse VVDI Super Chip for VVDI2 VVDI Mini Key Tool 10pcsLot
    $330.00
    Platinum resistance thermometer YET-710 high-precision probe 0.001 ℃ liquid gas thermometer YET-720L
    $317.46
    • Details
    • Reviews
    • Tags
    • FAQ
    Condition:New
    Type:Logic ICs
    Model Number:MB4TC
    Operating Temperature:W
    Supply Voltage:W
    Dissipation Power:W
    No.:TC MB4AI+
    Decoration and construction content:Hydropower project

    MB4TC 4 thermocouple high precision acquisition module, can be collected 8 kinds of thermocouple(J/K/T/E/R/S/B/N)Default K type, the acquisition of high precision temperature. 4 channels can be collected with the same type of thermocouple, can also be different for each channel type thermocouple; analog signal collected data, by isolating the RS485 interface output; module adopts Modbus-RTU communication, can be adapted to PLC, DCS and a variety of configuration software.


    The first chapter product introduction

    A.Summary

    MB4TC 4Thermocouple high precision acquisition module, can be collected 8 kinds of thermocouple (J/K/T/E/R/S/B/N), the acquisition of high precision temperature.4A channel can collect the same type of input, and each channel can be different input typesThe analog signal data collected by the isolated RS485 interface output module uses Modbus-RTU communication, can be adapted to DCS, PLC, and a variety of configuration software, etc..

    Signal acquisition, CPU and power input, RS485 communication electrical signal isolation, the effective suppression of all kinds of serial mode and common mode interference, to ensure the accuracy of the data, but also to ensure the reliability of the module.

    Two.Characteristic

    1.Using standard Modbus-RTU protocol.

    2.According to their own needs to set the input signal type channel.

    ThreeHigh precision signal acquisition: using high precision 24 bit AD and voltage reference, voltage reference temperature coefficient 10PPM/ C (max).

    4.Independent high precision cold end compensation, accuracy of 0.Five

    FiveSecurity: signal acquisition, signal output, power supply, RS485 communication electrical signals isolated from each other.

    SixCommunication protection: RS485 communication signal output interface using overvoltage and over current dual protection.

    7.Input signal type, communication format can be set through the software.

    8.Power polarity protection.

    Three.Technical index

    project

    parameter

    AI

    Signal input

    1Input channel: 4 channel isolated analog acquisition

    2Input signal type: 8 kinds of thermocouple ((J/K/T/E/R/S/B/N)

    ThreeSampling rate: 4 channels per 200mS acquisition again

    4Resolution: 24positionAD

    5.Signal acquisition circuit and CPU isolation voltage protection: 1500V

    DIAnd DO

    1.4Dry contact input optocoupler Commons

    2.4The way open collector output optocoupler Commons

    RS485

    Communication output

    1Communication protocol: MODBUS-RTU

    2Interface type: isolated RS485 communication, the output of the interface using the overvoltage and overcurrent protection

    3Baud rate: 1200BPS, 2400bps., 4800bps, 9600bps, 19200bps

    38400bps57600bps, 115200bps.

    4Check bit: no parity check, parity check

    5. setting: module address, baud rate, parity bits can be set by software

    6 RS485Circuit and CPU isolation voltage protection: 1500V

    Module size

    A.Separate module size: 104mm*72mm*26mm

    B.With terminal and guide rail box size: 124mm*72mm*45mm

    Installation method

    Standard DIN guide rail installation (35mm guide rail or high and low track)

    work environment

    Temperature: -10 ~ +55 temperature humidity: 35~85% (not dew)

    Working power supply

    1Power supply voltage: 10V~30V wide range of power supply, with the power supply polarity protection

    2Power consumption: less than 3W

    Four.measurement accuracy

    Input type

    measuring range

    Display resolution

    accuracy

    Thermocouple

    J(-200-1200 degrees C)

    0.1C

    + 0.4

    K(-200-1370 degrees C)

    T(-200-400 degrees C)

    E(-200-950 degrees C)

    R(-20-1750 degrees C)

    + 0.6

    S(-20-1750 degrees C)

    B(600-1800 degrees C)

    N(-250-1300 degrees C)

    + 0.4

    Cold end compensation

    -20 - 85

    0.1C

    Cold end compensation: + 0.5

    Five.Product appearance and external wiring diagram


    Six.Module indicator lamp and switch function specification

    1.POW/SET;Module working status indication

    A.Green light: the module works in the running state. B. red light: the module has the configuration parameters have been written, need to re power up.

    2.TXD/RXD:Communication status indication

    A.The green light flashes: the communication receives the data B. red light flashes: the module is sending data

    C.The green light is always on: DATA+ and DATA- on the communication line RS485 line is connected to the reverse or the connection is broken.

    ThreeModule right reset switch

    A.When the communication parameters (module address, baud rate, parity bit) do not know or communication parameter misspecification, and can not establish contact module communication, the solution is to reset the communication parameters; we use the clip to hold the reset switch is not open, 5 seconds after the [POW/SET] module of the red indicator lights, release the reset switch, the communication the parameters have been reset, as long as the power supply module after the restart time, the communication parameters of the module has been reset.

    B.Communication parameters after reset: Address: 1, baud rate: 9600bps, parity: No.

    Seven.Typical application wiring diagram


    Eight.Terminal definition

    terminal

    Name

    Explain


    terminal

    Name

    Explain

    1

    DI0

    Switch input 0

    26

    NC

    empty

    2

    AIGND

    Switch input 1

    25

    C3

    empty

    3

    IN1+

    Switch input 2

    24

    AI3-

    Thermocouple input channel 3 negative terminal

    4

    IN2+

    Switch input 3

    23

    AI3+

    Thermocouple input channel 3

    5

    DCOM

    Open in public

    22

    C2

    empty

    6

    DO0

    Switch output 0

    21

    AI2-

    Thermocouple Input Channel 2 negative terminal

    7

    DO1

    Switch output 1

    20

    AI2+

    Thermocouple Input Channel 2

    8

    DO2

    Switch output 2

    19

    C1

    empty

    9

    DO3

    Switch output 3

    18

    AI1-

    Thermocouple input channel 1 negative terminal

    10

    DATA+

    A RS485Communication +

    17