Technical parameter
Input voltage range:
D3: 4-36Vdc
A3: 90-430Vac
Input current: about 30mA
Reverse polarity protection: yes
LED indication: yes
Rated working voltage: 36-430Vac
Output on-state voltage drop: <2Vac
Off-state peak cut-off voltage: Vp≥900Vpk
Inrush current (one week of grid): 800%
Minimum load current: 100mA
Output leakage current: <10mA
Static voltage rise rate dVs/dt: 200V/μs
Commutation voltage rise rate dVc/dt: 200V/μs
Turn on response time does not exceed: 10ms
Turn-off time does not exceed: 10ms
Dielectric withstand voltage (between input, output and shell): ≥2000Vac
Insulation resistance (between input, output and shell): >1000MΩ (500Vdc)
Capacitance not exceeding: 10pf
Operating temperature range: -30℃~+80℃
Grid frequency: 47-63Hz



Product Characteristies
no contact
no spark
no noise
? ? ? ?Solid state relays work reliably, have no contacts, no electromagnetic interference, fast switching speed, strong anti-interference ability, and small size, vibration resistance, impact resistance, explosion-proof, moisture-proof, corrosion-proof, and can be compatible with TTL, DTL, HTL and other logic circuits Compatible, with a tiny control signal to directly drive a large current load.
Main circuit: 36-430Vac
Control terminal: 4-32Vdc, the control current does not exceed 15mA
Full isolation: The control terminal is isolated from the main circuit, with a withstand voltage of 3000V.
Control mode: DC control AC
Control voltage: 3-36VDC
On-off time: ≤10ms
Temperature range: -30℃~+80℃
On-state voltage drop: <2Vac



Selection rules
Calculate the current size
Equipment current ÷ coefficient = specification current
Specification current × coefficient = equipment current
Note: resistive load factor 0.2-0.3, inductive load factor 0.1-0.2
Note: The specification current is the inrush current, not the long-term working current
The current level and model of the relay load output terminal are as follows:

Note:
In the case of resistive load, the solid-state current level should be greater than or equal to 3 times the rated current of the load.
When the load is a DC motor, the solid-state current level must be greater than or equal to 5-6 times the rated current of the motor.
When connecting loads such as electromagnets and coils, the solid-state current level should be greater than or equal to 5 times the rated current of the load.
When connecting a capacitive load, the current level of the solid state must be greater than 10 times the rated current of the load.
Example: The load is a heating tube: three-phase 380V, each phase current is 15A.
Choose three-phase 50A solid state, model LSR-TH3Z50D3.