Three-phase power collection module , power acquisition module , three-phase electrical parameters acquisition module, acquisiti
Three-phase power collection module , power acquisition module , three-phase electrical parameters acquisition module, acquisiti
Three-phase power collection module , power acquisition module , three-phase electrical parameters acquisition module, acquisiti
Three-phase power collection module , power acquisition module , three-phase electrical parameters acquisition module, acquisiti
Three-phase power collection module , power acquisition module , three-phase electrical parameters acquisition module, acquisiti

Three-phase power collection module , power acquisition module , three-phase electrical parameters acquisition module, acquisiti

Price:   $87.99

  • Model: ic0A252
  • Shipping Weight: 0.2kg
  • 9999 Units in Stock

(0 reviews)
(complete orders today,deliverd around 25/04/2025)
  • Shipping time
    Shipping Worldwide.About 5-15 days.
  • means of transportation
    EMS,DHL,FEDEX,HK Post
  • Payment
    Paypal,T T,
  • Email us
    [email protected]
  • New Products
    100pcs 1206 SMD Chip Multilayer Ceramic Capacitor 43pF 62pF 3.9nF 6.8nF 18nF 20nF 27nF 56nF 330nF 680nF 820nF 0.33uF 0.68uF
    $1.56
    100pcs Chip Ceramic Capacitor X7R 0201 0402 0603 0805 120nF 0.12uF 180nF 330nF 0.33uF 390nF 470nF 0.47uF 560nF 25V 50V
    $2.86
    50PCS 2512 SMD Chip Fixed Resistor 1% 1W 0.1R 0.01R 0.05R 0.001R 0.33R 1R 0R 10R 100R 2W 0.001 0.01 0.1 0.33 0.05 1 0 10 100 Ohm
    $1.55
    100pcs 0603 50V SMD Thick Film Chip Multilayer Ceramic Capacitor 1pF - 22uF 10NF 100NF 1UF 2.2UF 4.7UF 10UF 1NF 100PF
    $1.35
    • Details
    • Reviews
    • Tags
    • FAQ
    Condition:New
    Type:Logic ICs
    Model:PD8073 - (xK) (xB)
    Item:2
    Renovation and construction content:Hydropower Engineering

    Three-phase full- power data acquisition module Introduction

    Model:PD8073 - (xK) (xB)

    One, Outline

    Monitoring requirements for power supply and distribution system design and manufacturing. High-precision powerASICChip measure active, reactive , apparent , voltage, current, frequency , power factor, four -quadrant21Harmonic power , dual-pulse output , phase sequence detection. WithRS485Communications interface for remote operation.

    Data for 32 -bit floating-point type , without any conversion , SCM, Kingview , PLC can be used directly .

    Optional alarm output, opto isolated output for connectionPLCSCM . Optically isolated triac outputs can directly drive AC contactor with zero trigger function.

    Module can directly replace conventional power transmitter for line counters , generators, energy management station . Yes, Kingview connection with the PLC. 6.53 provides a sample configuration king project.

    Members :
    Our advantage. We are not afraid of confinement .
    1 : Power supply options are AC85-265 DC10-30V DC24-72V AC85-450V, you might ask, why are so many choices? This DC24-72V used in communications base stations, because there is a spare battery 48V; AC100-450V used in this phase voltage supply ( without neutral) , the general design of the switching power supply can not afford.
    2 : using a dedicated power chip , 24 samples ( float ) . Other manufacturers generally are 16 samples ( integer ) .
    3: The sampling speed , sampled once per cycle , 50 times per second.
    4 : 32-bit floating-point data type , without any conversion , SCM, Kingview , PLC can be used directly . Many other manufacturers to do the data format is shaping different variables set different decimal point. So when Kingview , PLC with very troublesome, in accordance with the needs of different variables decimal conversion , in short, needs a lot of calculations.
    5: Electrical energy is not lost , permanent preservation. Whatever power failure test , the data will not be lost or confused . Some manufacturers of products powered down after power is cleared. Some frequent power outages , the resulting data confusion , power has become a big amazing.
    5: The phase sequence detection.
    6 : 485 opto-isolated , anti- AC380V interface can access two minutes without damage . Other manufacturers do not have this protection design.
    7 : Optional 1 alarm output , 8A600V or optocoupler triac output .
    Alarm or transmitter output, all in accordance with the percentage range of settings, parameters structure is completely unified . Alarm output has " hysteresis parameter " setting, his meaning is : for example UA Range 220V, high alarm point 110.0% , 5.0% hysteresis , delay 2 seconds , then action will follow the following rules : Continuous greater than 242V more than two seconds , output alarm ; once an alarm occurs , the voltage is lower than the 242-11 = 231V, only disarm the alarm .
    8 : powerful, almost all of the energy parameters are. PT, CT ratio , including the electric energy can be processed by the instrument , the data is the actual data obtained electricity . You can also choose not to take .
    All other manufacturers, if the data type is a 16-bit integer , are unable to complete the multiplication function. For example : if CT = 120 times . 65535 representative 65.535A, then 5A x 120 = 600A, with a 16-bit integer can not be expressed . And so. Lane said many manufacturers instructions : To take your own . This also means that if the variables defined in the configuration king IA, he is an integer type , but the actual IA should be equal ( communication integer ) / 1000 * CT ( ratio ) . Members : Many variables must be doing things like this . Tired of it. For more microcontroller PLC . And we use a standard float, as long as the definition of IA FLOAT get away . For details, please refer to " instrument configuration king 6.53 Project File" and " Meter MODBUS Quick Application Guide " we offer.
    9: own property , you can modify the program , and is compatible with any existing system . You can ensure that you do not modify the master program in the case, a direct replacement for other manufacturers equipment.

    You can specify when you need a compatible :( ordering)
    1 : " Gemotech " RemoDAQ-807X series register address , and is compatible with RemoDAQ-8000-9000 Series Utility software.
    Specific model : 8073S, 8073L, 8073 / B, 8073N / W
    2 : " a force " EDA9011X, EDA9033X series register address , and is compatible with "E Series test software ."
    Specific model : 9011 (A, D, E, G), 9033 (A, C), 9033_ power base can be set, 9033_ reported loss of pressure ,
    9033E (C), 9033G, 9033G, 9033K, 9033 ( Shida Rui sail custom )

    Two , Product Specifications

    PD8073 - (xK)

    Size:35mmRail mounting

    When ordering, please refer to : " Power Module Specification Sheet"

    Three , Measurement function

    Real-time data :

    Real-time data

    Symbol

    Three-phase voltage

    UA,UB,UC

    Three-phaseElectric current

    IA,IB,IC

    Three-phaseInstantaneous active power

    PA,PB,PC

    Total active

    PS

    Three-phaseInstantaneous Reactive Power

    QA,QB,QC

    Total reactive power

    QS

    Three-phaseInstantaneous apparent power

    SA,SB,SC

    The total apparent power

    SS

    Three-phasePower Factor

    PFA,PFB,PFC

    Total power factor

    PFS

    Three-phasePhoto corner

    ¢ A,¢ B,¢ C

    ThreeLine Voltage

    Uab,Ubc,Uca

    Grid frequency

    F

    Voltage reverse phase sequence indication

    Ubca

    Capacitive, inductive instructions

    RCLED,RLLED

    Energy data :

    Energy data

    Symbol

    Total active , total reactive power

    EP,EQ

    The total positive and negative active energy

    EPPS,EPNS

    The total positive and negative reactive energy

    EQPS,EQNS

    A,B,CPhase positive active energy

    EPPA,EPPB,EPPC

    A,B,CIn contrast to the active energy

    EPNA,EPNB,EPNC

    A,B,CPhase reactive power forward

    EQPA,EQPB,EQPC

    A,B,CIn contrast to the reactive energy

    EQNA,EQNB,EQNC

    Optional features :

    Alarm Output K

    OptionalDO1

    Transmission outputB

    OptionalAO1

    Fourth, Other technical parameters

    Accuracy class

    Accuracy class, start-up performance , creeping control , burst characteristic features:

    AccordGB / T17883,GB / T17215,GB / T 17882The relevant requirements.

    Instantaneous volume : ±0.5%

    Frequency : ±0.06Hz

    Power factor : ±0.001PF

    Energy error :+0.1 - +0.2( According to user requirements preset )

    Technical performance

    Pulse constant:As determined by the specification

    Voltage specifications :220V,57.7V,380V,100V,500,700V

    Current specifications :5A,30A,60A,120A,250A,400A,1000A

    Switch output :Opto- isolated outputs or optically isolated triac output(8A 600V).

    Switch output objects:Any one of the instantaneous volume can be specified as the output object.

    Communication module :IsolationRS485

    Voltage Impedance:2200K-3300K (With voltage specification changes)

    Current access methods :Transformers access .

    Linearity range:Voltage Range2Times the current range2Time

    Isolation voltage:Greater than all the isolation between the ports2KV

    Work Environment:Temperature-32-70 Relative humidity less than90% Non-corrosive gases

    Power supply:Optional Power Type:AC 85V-265V ( the default type ) / DC 8V-30V( Please specify when ordering ) / DC 32-72V ( 48V power communications base stations ) / AC100-450V ( phase power supply )

    Real-time clock function :Built- in lithium battery, after a power failure for at least5Years is not lost