Condition:New
Type:Logic ICs
Model:PD8073 - (xK) (xB)
Item:2
Renovation and construction content:Hydropower Engineering
Three-phase full- power data acquisition module Introduction
Model:PD8073 - (xK) (xB)
One, Outline
Monitoring requirements for power supply and distribution system design and manufacturing. High-precision powerASICChip measure active, reactive , apparent , voltage, current, frequency , power factor, four -quadrant21Harmonic power , dual-pulse output , phase sequence detection. WithRS485Communications interface for remote operation.
Data for 32 -bit floating-point type , without any conversion , SCM, Kingview , PLC can be used directly .
Optional alarm output, opto isolated output for connectionPLCSCM . Optically isolated triac outputs can directly drive AC contactor with zero trigger function.
Module can directly replace conventional power transmitter for line counters , generators, energy management station . Yes, Kingview connection with the PLC. 6.53 provides a sample configuration king project.
Members :
Our advantage. We are not afraid of confinement .
1 : Power supply options are AC85-265 DC10-30V DC24-72V AC85-450V, you might ask, why are so many choices? This DC24-72V used in communications base stations, because there is a spare battery 48V; AC100-450V used in this phase voltage supply ( without neutral) , the general design of the switching power supply can not afford.
2 : using a dedicated power chip , 24 samples ( float ) . Other manufacturers generally are 16 samples ( integer ) .
3: The sampling speed , sampled once per cycle , 50 times per second.
4 : 32-bit floating-point data type , without any conversion , SCM, Kingview , PLC can be used directly . Many other manufacturers to do the data format is shaping different variables set different decimal point. So when Kingview , PLC with very troublesome, in accordance with the needs of different variables decimal conversion , in short, needs a lot of calculations.
5: Electrical energy is not lost , permanent preservation. Whatever power failure test , the data will not be lost or confused . Some manufacturers of products powered down after power is cleared. Some frequent power outages , the resulting data confusion , power has become a big amazing.
5: The phase sequence detection.
6 : 485 opto-isolated , anti- AC380V interface can access two minutes without damage . Other manufacturers do not have this protection design.
7 : Optional 1 alarm output , 8A600V or optocoupler triac output .Alarm or transmitter output, all in accordance with the percentage range of settings, parameters structure is completely unified . Alarm output has " hysteresis parameter " setting, his meaning is : for example UA Range 220V, high alarm point 110.0% , 5.0% hysteresis , delay 2 seconds , then action will follow the following rules : Continuous greater than 242V more than two seconds , output alarm ; once an alarm occurs , the voltage is lower than the 242-11 = 231V, only disarm the alarm .
8 : powerful, almost all of the energy parameters are. PT, CT ratio , including the electric energy can be processed by the instrument , the data is the actual data obtained electricity . You can also choose not to take .
All other manufacturers, if the data type is a 16-bit integer , are unable to complete the multiplication function. For example : if CT = 120 times . 65535 representative 65.535A, then 5A x 120 = 600A, with a 16-bit integer can not be expressed . And so. Lane said many manufacturers instructions : To take your own . This also means that if the variables defined in the configuration king IA, he is an integer type , but the actual IA should be equal ( communication integer ) / 1000 * CT ( ratio ) . Members : Many variables must be doing things like this . Tired of it. For more microcontroller PLC . And we use a standard float, as long as the definition of IA FLOAT get away . For details, please refer to " instrument configuration king 6.53 Project File" and " Meter MODBUS Quick Application Guide " we offer.
9: own property , you can modify the program , and is compatible with any existing system . You can ensure that you do not modify the master program in the case, a direct replacement for other manufacturers equipment.
You can specify when you need a compatible :( ordering)
1 : " Gemotech " RemoDAQ-807X series register address , and is compatible with RemoDAQ-8000-9000 Series Utility software.
Specific model : 8073S, 8073L, 8073 / B, 8073N / W
2 : " a force " EDA9011X, EDA9033X series register address , and is compatible with "E Series test software ."
Specific model : 9011 (A, D, E, G), 9033 (A, C), 9033_ power base can be set, 9033_ reported loss of pressure ,
9033E (C), 9033G, 9033G, 9033K, 9033 ( Shida Rui sail custom )
Two , Product Specifications
PD8073 - (xK)
Size:35mmRail mounting
When ordering, please refer to : " Power Module Specification Sheet"
Three , Measurement function
Real-time data :
Real-time data | Symbol |
Three-phase voltage | UA,UB,UC |
Three-phaseElectric current | IA,IB,IC |
Three-phaseInstantaneous active power | PA,PB,PC |
Total active | PS |
Three-phaseInstantaneous Reactive Power | QA,QB,QC |
Total reactive power | QS |
Three-phaseInstantaneous apparent power | SA,SB,SC |
The total apparent power | SS |
Three-phasePower Factor | PFA,PFB,PFC |
Total power factor | PFS |
Three-phasePhoto corner | ¢ A,¢ B,¢ C |
ThreeLine Voltage | Uab,Ubc,Uca |
Grid frequency | F |
Voltage reverse phase sequence indication | Ubca |
Capacitive, inductive instructions | RCLED,RLLED |
Energy data :
Energy data | Symbol |
Total active , total reactive power | EP,EQ |
The total positive and negative active energy | EPPS,EPNS |
The total positive and negative reactive energy | EQPS,EQNS |
A,B,CPhase positive active energy | EPPA,EPPB,EPPC |
A,B,CIn contrast to the active energy | EPNA,EPNB,EPNC |
A,B,CPhase reactive power forward | EQPA,EQPB,EQPC |
A,B,CIn contrast to the reactive energy | EQNA,EQNB,EQNC |
Optional features :
Alarm Output K | OptionalDO1 |
Transmission outputB | OptionalAO1 |
Fourth, Other technical parameters
Accuracy class
Accuracy class, start-up performance , creeping control , burst characteristic features:
AccordGB / T17883,GB / T17215,GB / T 17882The relevant requirements.
Instantaneous volume : ±0.5%
Frequency : ±0.06Hz
Power factor : ±0.001PF
Energy error :+0.1 - +0.2( According to user requirements preset )
Technical performance
Pulse constant:As determined by the specification
Voltage specifications :220V,57.7V,380V,100V,500,700V
Current specifications :5A,30A,60A,120A,250A,400A,1000A
Switch output :Opto- isolated outputs or optically isolated triac output(8A 600V).
Switch output objects:Any one of the instantaneous volume can be specified as the output object.
Communication module :IsolationRS485
Voltage Impedance:2200K-3300K (With voltage specification changes)
Current access methods :Transformers access .
Linearity range:Voltage Range2Times the current range2Time
Isolation voltage:Greater than all the isolation between the ports2KV
Work Environment:Temperature-32-70 Relative humidity less than90% Non-corrosive gases
Power supply:Optional Power Type:AC 85V-265V ( the default type ) / DC 8V-30V( Please specify when ordering ) / DC 32-72V ( 48V power communications base stations ) / AC100-450V ( phase power supply )
Real-time clock function :Built- in lithium battery, after a power failure for at least5Years is not lost